Enfinity® Console In-Room Water Source Heat Pumps

Unsurpassed reliability and quiet operation

enfinity

More than 40 years ago, Daikin designed the first complete line of water source heat pumps for high efficiency, individually zoned comfort control in offices, schools, assisted living facilities, manufacturing facilities and other commercial buildings. Our reputation for outstanding reliability and quiet operation has been reinforced in thousands of successful installations.

Enfinity water source heat pumps incorporate the best of our past and the best of what's new. Using feedback from building owners, consulting engineers, contractors and service engineers, we designed Enfinity products to give you maximum flexibility to design, install, operate and maintain the ideal water source heat pump system for your building project.

  • Standard or geothermal application flexibility
  • High efficiency reduces energy consumption/operating costs and can contribute to earning LEED® points and rebates
  • GentleFlo® cross-tangential fan wheel design provides whisper quiet operation and maximum airflow for proper air circulation
  • MicroTech® III unit controls with Open Choices® feature allows standalone or easy, low cost network integration using LonWorks® or BACnet® communication options
  • Two cabinet styles – flat top or slope top in high or low sill configuration to satisfy special application requirements
  • Performance rated with ISO Standard 13256-1
  • eQuest® Ready! Click here to download product input files for use with eQUEST® energy modeling software.

Specifications

Enfinity Console In-Room Dimensions
Unit Size Dimensions
L W H
007 (low sill) 10.25 46 22.5
007 (high sill) 10.25 46 25
009 (low sill) 10.25 46 22.5
009 (high sill) 10.25 46 25
012 (low sill) 10.25 54 22.5
012 (high sill) 10.25 54 25
015 (low sill) 10.25 54 22.5
015 (high sill) 10.25 54 25
018 (low sill) 10.25 54 22.5
018 (high sill) 10.25 54 25
Enfinity Console In-Room Performance Data

Unit Size
Air Flow
Water Flow
Water Loop (standard unit) Ground Loop (ECM & high static)
Cooling Heating Cooling Heating
cfm L/S GPM L/S Btu/hr EER Btu/hr COP Btu/hr EER Btu/hr COP
007 295 139 1.9 0.12 7700 14.5 9110 5.0 8300 16.9 5600 3.3
009 355 167 2.4 0.15 9200 14.0 11,000 4.6 9700 16.1 7000 3.2
012 370 175 2.9 0.18 11,000 13.1 13,700 4.3 11,700 15.3 8900 3.2
015 535 252 3.7 0.23 14,500 15.1 18,200 5.2 15,400 17.3 10,900 3.4
018 485 229 4.6 0.29 16,400 13.4 20,900 4.3 17,300 15.3 13,200 3.4

Resources